Cutterpup wrote:Bruce, don't get hot under the collar. Just show me a specification or a regulation fron NEC or CEC ...
<snip>
Dan
Me hot? No way.

And don't expect a straight answer. Here's as straight as it gets:
Here's the NEC sections:
II. Branch-Circuit Ratings
210.19 Conductors — Minimum Ampacity and Size.
1) General. The ampacity of branch-circuit conductors shall not be less than 125 percent of the designed potential load of utilization equipment that will be operated simultaneously.
210.20 Overcurrent Protection.
Branch-circuit conductors and equipment shall be protected by overcurrent protective devices that have a rating or setting that complies with 210.20(A) through (D).
(A) Continuous and Noncontinuous Loads. Where a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less than the noncontinuous load plus 125 percent of the continuous load.
Exception: Where the assembly, including the overcurrent devices protecting the branch circuit(s), is listed for operation at 100 percent of its rating, the ampere rating of the overcurrent device shall be permitted to be not less than the sum of the continuous load plus the noncontinuous load.
Here's an interpretation:
Branch and Feeder Circuits
For branch circuits, NEC 210.19 states the rules for sizing conductors. The general rule is that conductors are sized to have an ampacity of not less than the noncontinuous load plus 125 percent of the continuous load. The corresponding rule for overcurrent protection is given in NEC 210.20(A). It states that the OCPD rating is to be not less than the noncontinuous load plus 125 percent of the continuous load. According to the definition in Article 100, continuous load means that it continues for 3 hours or more. Similar rules for feeders appear in NEC 215.2 and 215.3. Two points are clear:
• Ampacity of the conductors is matched to OCPD rating by the same rule.
• OCPDs are sized for 125 percent of continuous current, which means that they are expected to carry continuously 80 percent of rated current.
Those points don't seem that clear to me but there you have it.
Bruce