Hi I know that this is not a T&TTT type question, but hopefully someone can explain this to me. My new(to me) hot tub requires a 4 wire hook up.. that is black 120v, red 120v, white neutral and green ground. The main panel in the house has the white and green ground going to the same bus bar. So far every sparktecian has said to me to run the white and the ground all the way back to the main panel, HOWEVER the hot tub is being run off a sub panel that has only the 3 wires in it (red/black/green) then to a GFI disconnect breaker which has the 4 wires. So the QUESTION is since the white and ground are the same in the main can I run the white only to the sub panel or do I have to run it another 30 feet and connect it to the same bus as the ground wire?
Thanks and I will invite the gang over for some stargazing and liquid libations
Dan